Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM04689
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS ITEMS 1,2,3 & 5 2. FILL UNUSED OPENINGS IN BOXES |
|
07/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK ROOF 1. WE HAVE BOX OVERFILL 2. SUPPORT M/C CABLE WITHIN 12" OF BOXES AND AS PER 300.11 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 4. SUPPORT VDV CABELING UP OFF OF GRID 5. TIGHTEN LOOSE FITTINGS. 6. THHN IS NOT AN APPROVED SUPPORT METHOD. 7. WE HAVE A BROKEN M/C ARMOR TO AN EXISTING LIGHT |
|
04/25/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/19/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TCO PHASE ONE ONLY OK WALL DUCT |