Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/25/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE AND RECHECK ALL ITEMS AS CALLED OUT FROM LAST INSPECTIONS 2) FIRESTOP ALL NON-INSULATED INTERIOR TOP PLATES 3) SEPERATE ALL FLEX DUCT AND METAL GUSSET PLATES AT TRUSSES 4) SEPERATE ALL ROMEX AT METAL GUSSET PLATES AT TRUSSES |
|
| 05/21/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AS BUILT GAS LINE TOTAL DEVELOPED LENGTH EXCEEDS 60'-1" SUPPLY LINE INSUFFICIENT FOR PROPOSED DEMAND 2) PROVIDE COMBUSTION AIR VENTS PER PLAN 3) FILL DWV FOR TEST 4) PROTECT DRYER DUCT AT TOP PLATE 5) PROTECT CONDENSATE DRAIN 6) BLOCK ROOF SHEATHING AT SUPPLY AND RETURN AIR DUCTS 7) COMPLETE ATTIC ACCESS IN LAUNDRY 8) INSTALL FAN RATED OUTLET BOXES WITH SCREWS IN CORRECT HOLES 9) MOVE LIGHT OUTLET IN PANTRY TO PROVIDE 12" CLEARANCE FROM SHELF LINE 10) PROTECT PLUMBING LINES IN KITCHEN 11) SECURE HOLDOWN STRAPS TO PORCH BEAM |
|
| 04/03/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INTERMEDIATE INSPECTIONS MUST BE COMPLETE PRIOR TO FRAMING INSPECTION 2. REFEE WILL APPLY |
|
| 12/13/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) ALL INTERMEDIATES MUST BE COMPLETE PRIOR TO FRAMING INSPECTION 2) RECALL FOR EXT. CLIP AND ROOF NAILING INSPECTIONS AND PROVIDE ROOF ACCESS |