Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T05CM04642
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1. OK FOR CEILING TILES. 2. LEAVE OUT UNDER EACH FAN COIL. 3. NEED TO SEE DUCT SMOKE DETECTORS. 4. ON FINAL PROVIDE A SMOKE TEST. 5. RELOCATE LINE SET FAN COIL 4 BLOCKING ACCESS |
|
12/07/2006 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* DRAIN PANS MUST EXTEND MIN. 1 1/2" BEYOND ALL SIDES OF FAN COILS. IDENTIFY FAN COILS. REFER LINES BLOCKING ACCESS TO FAN COIL. PROVIDE SECONDARY DRAIN SMALL FAN COIL. PROVIDE BUSHINGS IN CABINETS FOR REFER LINES. SECURE LOW VOLTAGE WIRE AS PER NEC |