Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05CM04642
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
02/13/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PLASTIC TO IRON PIPE CONNECTION SHALL BE PLASTIC MALE IRON PIPE THREADS TO FEMALE IRON PIPE CONNECTION. WATER TO BE ON TO LANDSCAPING SUPPLY TO TEST FITTINGS SECURE & MAKE WATER TIGHT URINAL IN MENS RESTROOM. |
|
02/05/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) YOUR CONNECTION FOR LANDSCAPING WATER SUPPLY SHALL BE A TEE FITTING NOT A TAP 2) LOWER LEVEL FLOOR DRAINS TO BE FLUSH WITH FINISH FLOOR TO PREVENT TRIPPING HAZARD 3) WILL RECEIVE LANDSCAPING BACKFLOW CERTIFICATION AT FINAL APPROVAL |
|
12/22/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* LEAKING FLUSHOMETER WOMENS CAULKING AT UPSTAIRS URINAL SUPPORT PVC FOR ELEVATOR PUMP USE FACTORY TAPPED CO PLUG IN ALL LOCATIONS FLOOR DRAINS ARE TOO LOW IN LOWER TOILET RMS - CONTINUED BELOW RECEIVED TWO BACKFLOW CERTS FOR FOUNTAIN AND PLANTER. NEED BACKFLOW CERT FOR IRRIGATION, DATED AFTER REINSTALLATION. I SEE NO SAFETY HAZARDS THAT MIGHT PREVENT A TEMP C OF O |
|
12/21/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*. CONTRACTOR CANCELLED |
|
12/20/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE ALL PLUMBING FIXTURES PROVIDE WATER TIGHT SEAL, PROVIDE CLEANOUTS AS REQUIRED WITH COVERS, PROVIDE BACKFLOW CERTIFICATIONS, WATER HEATER TO BE PIPED PER PLAN. WATER SUPPLY FOR LANDSCAPING BACKFLOW DEVICE TO BE PROPERLY SUPPLIED AND HAVE OK FROM TUCSON WATER TO BE UPSTREAM OF BUILDING BACKFLOW DEVICE. NOT COMPLETE LIST |