Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T05CM04642
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2006 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
12/07/2006 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* | |
09/12/2006 | PLUMBING - PROGRESS | Partial Approval | VERTICAL SUPPORTS ON ROOF DRAINS OK STILL NEED TO MAKE CORRECTIONS ON PIPING AND TEST |
|
09/08/2006 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT 1ST FLOOR RESTROOMS 122, 124 104 AREA TO 2ND LEVEL 2' AFF INCLUDING BREAKROOM SINK 119 OK. 1. ALL PIPING TO HAVE CORRECT SUPPORT IN WALL SIK OFFICE 129 WATER TEST THRU ROOF OK 2ND LEVEL SANITARY DRAINAGE TO 2' AFF AT 2ND LEVEL FOR RESTROOM 202 WATER TEST OK. 2. SHALL TEST WASTE & VENT THRU ROOF 3. SANITARY DRAINAGE FOR 2ND LEVEL RESTROOM 221 & 223 SHALL BE TESTED FROM 1ST LEVEL. WATER DISTRIBUTION 1ST LEVEL 100 PSI TEST OK 4. RESTROOM 122 & 124 CW TO STOOLS TO BE PER PLAN. 5. SHALL MAKE ACCOMODATION FOR INSULATION PER PLAN SPEC ON ALL HOT WATER PIPING. |