Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM04642
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FINISH PREVIOUS ITEMS-VERIFY LOCATION OF REMOVED CORDS |
|
12/22/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROPERLY SUPPORT VDV CABELING 760.6/725.6 2. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 OK FOR TEMP C OF O |
|
12/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT FINISHED NO CEILING INSPECTION 2ND FLOOR 1. TO MANY LOOSE ENDS 2. 2ND FLOOR CEILING NOT INSPECTED |
|
12/20/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE OUTSIDE LTG. POLE LTS. 2. PLANTER IN ENTRY AREA 3. FLOOR BOX RECEPT. NOT INSTALLED COMPLETE LIGHT FIXTURES IN CEILINGS. 4. POND NOT WIRED YET 5. NO ACCESS INTO 2ND FLOOR ELECTRIC ROOM - DUE TO CARPET GLUE. 6. OK PANEL SLA IN COMP. ROOM 7. SOUTH CANOPY LTG NOT COMPLETE 8. OK ROOF ELECTRIC |