Permit: T05CM04642

Parcel: 135074470


Addresses:

1490 S EASTSIDE LP


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM04642

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/11/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
12/07/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. SECURE FIXTURES TO GRID 4 ON CORNERS
ALSO, MANUFACTURE CLIPS TO BE EFFECTIVE.
2. SUPPORT VDV CABLING PER 725.6, 760.6, 800.6
3. INSTALL EXIT LIGHTS
4. MAINTAIN CLEARANCE FOR A/C DISCONNECTS
5. CHECK BOX BILL PER 314.16
6. SUPPORT WIRES NEED FOR FIXTURES
7. GFI TESTING PER 230.95