Permit: T05CM04618

Parcel: 116260180

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/03/2006 BUILDING - FINAL Approved IVRS - Inspection :*
05/02/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A/C OVER FUSED
2) BREAK OFF SMALL BOLT ON ANTI-SIPHON HOSE BIBS
3) INSTALL SMOKE DETECTORS INSIDE EXISTING BEDROOMS
4) NO POWER TO BATH GFCI
5) NEED ACCESS DOOR TO EQUIPMENT JACUZZI
04/25/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CAULK AROUND BASE OF TOILET
2) NEED LADDER TO INSPECT ROOF TOP A/C
3) NO POWER TO BATH GFCI RECEPTACLES
4) INSTALL SMOKE DETECTORS EXISTING BEDROOMS
5) BREAK OFF SMALL BOLT ON ANTI-SIPHON DEVICE HOSE BIB
6) PATCH DRYWALL AROUND ELECTRIC BOXES, SWITCHES, ETC...
7) STOPPED INSPECTION
04/11/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT GAS PIPING ON ROOF
2) INSTALL ANTI-SIPHON HOSE BIB
3) CUT SEWER CLEANOUTS TO GRADE
4) PAINT EXPOSED PLUMBING VENT ON ROOF
5) GATE LOCKED
6) CANNOT CLIMB OVER BLOCK WALL
7) NEED LADDER TO INSPECT ON ROOF
8) STOPPED INSPECTION