Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM04609

Parcel: 12205039F


Addresses:

4409 E SENECA ST


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T05CM04609

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2006 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*