Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05CM04596
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1. REVISED APPROVED PLAN ON SITE. 2. PRESSURE TEST OK 3. CORRECTIONS MADE OK - ONE EXCEPTION 1 1/2" DROP TO PIZZA OVEN - REQUIRE 1 1/2" TO EACH BRANCH. WILL CHECK ON FINAL. |
|
05/08/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE REVISED APPROVED PLAN OF YOUR GAS DISTRIBUTION STYSTEM. 2. SUPPORT GAS PIPING OVERHEAD, AT ROOFTOP UNITS, AND AT DROPS FOR APPLIANCES IN BUILDING. |