Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 04/12/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE DETAIL SHOWING TRUSS HANGERS AS THD26 APPROVED BY PLAN CHECK 2) NEED SIMPSON HTT22 HD'S AT DINING ROOM-PAGE 2 OF DRAWINGS 3) NEED RECEPTACLES BOTH SIDES OF OFFICE ENTRY-WALLS OVER 2' LONG 4) DOOR BELL TRANSFORMER CANNOT BE LOCATED IN CLOSET 5) NEED RECEPTACLE SOUTH OF ENTRY IN GREAT ROOM 6) NAIL STOPS DRYER VENT AT BLOCKING 7) GAS PRESSURE LESS THAN 1 POUND 8) NEED ACCESS PANEL FOR MASTER TUB 9) NEED ADDITIONAL FRAMING FOR SHEETROCK LIDS BOTH FURNACE ROOMS 10) STUCCO MESH MUST BE INSTALLED PRIOR TO APPROVAL OF INTERMEDIATES |
|
| 03/21/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) AT FRAME INSPECTION NEED H.D.'S AT DINING ROOM 2) NEED TRUSS CALC'S 3) NEED SIZES OF LU HANGERS. NOT SPECIFIED ON FRAMING DETAILS 4) PROCEED AT OWN RISK UNTIL TRUESSES VERIFIED WITH CALC'S |
|
| 03/20/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1. ADD A35s PER DETAIL 6.6 AT LEDGERS 2. 6 16d EACH STUD PER DETAIL 6.6 3. CHECK TRUSSES FOR PLUMB & WITHIN TOLERANCES 4. NO TRUSS CALCS ON SITE TO DETERMINE WHAT SIZE LU HANGERS REQUIRED. 5. ADD INTERIOR H/D AT DINING ROOM 6. EXTERIOR SIDING NAILING AND CLIPS OKAY 7. OK TO WRAP AND DRY IN |