Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM04554
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2005 | FRAMING | Approved | IVRS - Inspection :* | |
12/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOME RUN LINES REQUIRES SEPERATION 2) TO MANY WIRES PER STAPLE 3) PROTECT WIRES FROM TRUSS GANG PLATES OVER MASTER BATH AND 220 OVER MASTER CLOSET 4) ABS OUT OF WALL MASTER BATH 5) SECURE WIRES AT S.G.D. 6) PROTECT CONDENSATE DRAINS AT TOP PLATE 7) BLOCK SHEAR AT FRONT BED WHERE PANEL IS CUT 8) FRESH AIR INTAKE REQUIRES 10' MINIMUM CLEARANCE TO EXHAUST 9) REPLACE CRIPPLES IN FRONT BEDROOM 10) COMPLETE H.D. FRONT BED 11) SEAL ALL PENETRATIONS THROUGH LATH |