Permit: T05CM04553

Parcel: 118272810

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM04553

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
03/15/2006 FRAMING Approved IVRS - Inspection :*
12/19/2005 FRAMING Partial Approval IVRS - Inspection :*
1) PENDING ENGINEERING
12/14/2005 FRAMING Partial Approval IVRS - Inspection :*
1) PENDING ELECTRIC
2) NEED ENGINEERING
3) STUCCO SEALED INSIDE
4) APPROVED TO INSULATE
12/09/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FAN BOXES NOT INSTALLED PER PLAN
2) OVERSPAN WEST WALL
3) SHIM HEADERS WHERE NEEDED
4) VTR NOT 10 FT FROM FRESH AIR
5) MOVE ALL ELECTRIC WIRES FROM GUSSET PLATES
6) PROVIDE ENGINEERING FOR POST TENSION JACK HAMMERED AT MASTER WATER CLOSET
7) 12/3 WIRE HANGING IN LAUNDRY ROOM
8) DWV CIRCUIT NOT MADE UP
9) ITEM 03050 NOT REQUIRED-NO GAS/ALL ELECTRIC