Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/19/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. LIGHTING IS NOT PER PLAN 2. SUPPORT WIRES NEEDED FOR ALL FIXTURES AND EQUIPMENT MUST BE SEPARATE FROM GRID SUPPORT AND SECURED @ BOTH ENDS. 3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND NO MORE THAN 6' THEREAFTER. 4. ALL BOXES CONTAINING FIRE ALARM TERMINATIONS TO BE IDENTIFIED. |
|
| 09/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDERGROUND COVER TO CASH WRAP |
|