Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2006 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
| 03/31/2006 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO CORRECTIONS MADE AS REQUESTED. ADDING MORE MUD TO COVER FACT THAT YOU DID NOT USE CEILING ROCK IN SEVERAL AREAS IS NOT OK! PLEASE NOTE THIS IS THE 2ND TIME THAT THIS BUILDER HAS ATTEMPTED TO USE CHEAP TRICKS TO TRY AND FOOL ME. IF YOU DON'T LIKE YOUR PLAN THEN REVISE IT! PLEASE DON'T ATTEMPT MORE TRICKERY. |
|
| 03/29/2006 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ATTIC ACCESS PANELS REQUIRED. 2. CEILINGS REQUIRE 1/2" CEILING ROCK PER PLAN. 3. PROVIDE ACCESS FOR ABOVE CEILING INSPECTION. |
|
| 03/27/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* 1. STILL NEED TO FIRE CAULK (@ PARTY WALL) ANY JOINTS LARGER THAN 1/16" & ANY PENETRATIONS. PLEASE PROVIDE SYSTEM FOR U.L LISTED INTUMESCENT CAULK. |
|
| 03/24/2006 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* GATES LOCKED, NO ACCESS TO JOBSITE @ 2:56 |
|
| 03/13/2006 | SHEET ROCK NAILING | Not ready for Inspection | IVRS - Inspection :* 1) REMEMBER ROCK ON PARTY WALL MUST GO TO ROOF DECK |