Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM04519

Parcel: 12801017E


Addresses:

1010 S WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T05CM04519

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
05/05/2006 ELECTRIC - UNDERGROUND Approved
04/25/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK TO CLEAR IMC IN TRENCH
2) FINISH PREVIOUS ITEMS #7 & #9
04/24/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING ELECTRODE CONDUCTOR TO BE TERMINATED TO GROUNDED CONDUCTOR.
2. NEED BOTH REJECTION PINS.
3. BOND METER SOCKET.
4. BOND SERVICE NIPPLE 250.92
5. BOND RISER
6. UNCOVER CONDUITS FOR UNDERGROUND INSPECTION.
7. USE APPROVED FITTINGS WITH LB
8. SUPPORT CONDUIT
9. SEAL ENTRANCES ABOVE CURRENT CARRYING PARTS.
03/31/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*