Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T05CM04519
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2006 | ELECTRIC - UNDERGROUND | Approved | ||
04/25/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR IMC IN TRENCH 2) FINISH PREVIOUS ITEMS #7 & #9 |
|
04/24/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING ELECTRODE CONDUCTOR TO BE TERMINATED TO GROUNDED CONDUCTOR. 2. NEED BOTH REJECTION PINS. 3. BOND METER SOCKET. 4. BOND SERVICE NIPPLE 250.92 5. BOND RISER 6. UNCOVER CONDUITS FOR UNDERGROUND INSPECTION. 7. USE APPROVED FITTINGS WITH LB 8. SUPPORT CONDUIT 9. SEAL ENTRANCES ABOVE CURRENT CARRYING PARTS. |
|
03/31/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* |