Permit: T05CM04503

Parcel: 13218171D


Addresses:

4875 S PARK AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/27/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/23/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PNL C - SCHEDULE DOES NOT READ AS PLAN NOTES IF RECEPTACLES ARE DEDICATED MARK ON PANEL SCHEDULE RATHER THAN JUST RECEP.
2. NO DOUBLE POLE 40 AMP. BREAKER LISTED ON PANEL
3. LABEL PNL "C" PNL "D"
4. LABEL MAIN DISCONNECT FOR D
5. PNL D NOT AS PER PLAN
6. CONDUIT ONLY
10/26/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WIRING TO NEW COOLER NOT TO CODE, ROMEX ABOVE CEILING TO BE APPROVED FOR THIS INSTALLATION BY ARCH. & SUPPORTED TO CODE, SEE NOTES FROM INSPECTION ON 10/17/05
10/17/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*REVISE PLAN SHOW WORK AS INSTALL, INCLUDE ANY DELETED EQUIP FROM PLAN.
SUPPORT CABLING, MC ABOVE CEILING PER NEC. REVISE FOR USE OF NM TO BE APPROVED BY ARCH.