Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/30/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1. FIRESTOP SECOND FLOOR PENETRATIONS 2. ANCHOR BOLTS MISSING GARAGE SHEER WALL 3. HOLD DOWNS MISSING GARAGE SHEAR WALL 4. STAIRS EXCEED 3/8" RISE DIFFERENCE 5. SHEAR WALL SILL PLATE NOT NAILED PER PLAN 6. FIRE STOP MECH CHASE 7. FURNACE NOT INSTALLED PER INSTALLATION MANUAL 8. PROVIDE AN ORIGINAL FURNACE INSTALLATION MANUAL 9. MASTER BATH TOILET NOT PROPERLY VENTED 10. FIRE STOP FIRE PLATE CHASE STOPPED INSP. NEXT FAILURE WILL REFEE |
|
| 01/24/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL ALL PENETRATIONS THRU LATH 2) TIGHTEN ALL AB'S 3) FIRESTOP 2ND FLOOR PENETRATIONS THROUGHOUT 4) PROTECT COPPER TUBING AT TOP PLATE BY WATER HEATER 5) AB MISSING BEHIND FIREPLACE AND GARAGE SHEARWALL 6) CONMPLETE H.D.'S 7) FLOOR TRUSS CUT AT STAIRWAY 8) CLIP STUDS AT INTERIOR BEARING WALL BEHIND H. BATH SHOWER 2ND FLOOR 9) FIRESTOP CAHSE AT H. BATH 2ND FLOOR 10) FIREBLOCKS MISSING AT BED/GARAGE 11) NUMBER OF CLOSETS EXCEEDED FOR B-VENT 12) STOPPED INSPECTION-TO MANY ITEMS |