Permit: T05CM04487

Parcel: 10511043B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/29/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/26/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROPERLY SUPPORT ALL LOW VOLTAGE WIRING NEC 800.6
2) SUPPORT FLEX OFF GRID AND CLOSE OPEN J-BOX ( IN HALL )
3) OK TO PUT TITES IN AFTER CORRECTIONS-I WILL CHECK ON FINAL
4) PROVIDE LADDER
05/23/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. INSTALL K.O BLANKS IN BOXES AS NEEDED
2. REMOVE/SAFE OFF OPEN WIRING (PROGRAM MAN.) AND PROJECTOR SCREEN AREA.
3. MAKE SURE NO OVERFILLED BOXES - I CAN'T TELL WHAT'S NEW OR OLD.
OK TO COVER CEILING AFTER THESE THINGS TAKEN CARE OF
DON'T RECALL I'LL CHECK ON FINAL.