Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/05/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY SUPER |
|
| 11/30/2005 | FRAMING | Cancelled | IVRS - RI canceled | |
| 11/29/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) SHEARWALL #8 NOT NAILED AT 4" AND 12" 2) PROVIDE APPROVED DETAIL FOR GARAGE #8 SHEARWALL CONNECTION TO TRUSS SYSTEM OR COMPLY WITH 6/SD3-REMOVE WIRES 3) DUCT WORK CANNOT BE ? MORE THAN 1/3 4) 6/SD3 NOT COMPLIED WITH AT BEDROOM 3 SHEARWALL 5) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE 6) BEDROOM 3 #8 SHEARWALL NOT NAILED PER PLAN 7) STOPPED INSPECTION-TOO MANY ITEMS |
|
| 11/23/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED HANGERS HIP JACK TRUSSES AND JACK TRUSSES IN GARAGE 2) COMPLETE ACCESS TO FURNACE 3) NAIL AND BOLT H/D SOUTH WEST CORNER 4) IF BAR TOP EXTENDS OVER 6" REMOVE RECEPTACLE L/R SIDE 5) #12 AND #14 SAME BOX 6) INSURE SMOKE DETECTOR BETWEEN 6 + 12" OF CEILING 7) NO DWV WATER TEST 8) SUPPLY OK 9) DUCT ENCROACHES ON AA 10) ITEM 03050 NOT APPLICABLE PER PAPERWORK TURNED IN BY INSPECTOR W. NORTH |