Permit: T05CM04440

Parcel: 12810080A


Addresses:

200 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM04440

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/20/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/19/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
04/16/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1ST FLOOR
1. PREVIOUS INSPECTION ITEM CORRECTED
NEED TO CHECK LOW VOLTAGE CONNECTIONS ON AIR HANDLERS & FUSING AT DISCONNECTS AT FINAL.
04/12/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CORD CAP CANNOT BE CUT OFF OF CONDENSATE PUMPS VIOLATED LISTING.
PUMPS NEED TO BE PLUGGED IN TO RECEPTACLE OUTLET PER NEC 400.7 B
2. PANEL "A" OK TO ENERGIZE
04/06/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/05/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/15/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK SOFFIT AREAS IN LOBBY ROOM 102
OK SOFFIT AREA DRIVE THRU OUTSIDE