Permit: T05CM04409

Parcel: 13318007M


Addresses:

7000 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM04409

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/09/2005 PLUMBING - FINAL Approved IVRS - Inspection :*DWV WATER TEST IS OK
ALL CORRECTIONS HAVE BEEN MADE
11/04/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*NO HUB COUPLING IS ONLY APPROVED ON NO HUB CAST IRON.USE SOLVENT ?? COUPLING FOR ABS
SUPPORT ALL PIPING IN CORRECT MANNER
10/27/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*EXPOSE WATER & SEWER CONNECTIONS UNDERGROUND.
CANNOT LOCATE A C.O TEE IN A HORIZONTAL POSITION USE A TWO WAY C.O
REMOVE FERNCO COUPLING AND REPLACE WITH APPROVED COUPLING
A BLOCK( MASONRY) IS NOT AN APPROVED METHOD OF BLOCKING SEWER LINE.
PROVIDE A WATER TEST ON BLDG SEWER
PROVIDE A VACUUM BRAKER @ HOSE BIB
INSULATE DOMESTIC WATER SUPPLY UP TO MODUAL