Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/18/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WH B-VENT REQUIRES 1" TO COMBUSTIBLE MATERIAL AND MUST EXTEND 1" BELOW DRYWALL 2) PROVIDE ENGINEERING FOR NOTCHED TRUSS ABOVE KITCHEN 3) REVERSE PITCH POWDER ROOM VENT 4) SUPPORT HORIZONTAL DWV AT 4' ON CENTER 5) REVERSE PITCH W/H B VENT 6) MAX ALLOWED STAIR BULL NOSE 1 1/4" 7) SECONDARY CONDENSATE MUST EXHAUST IN A CONSPICOUS LOCATION OVER WINDOW 8) SEAL 2ND FLOOR PENETRATIONS 9) FURNACE NOT COMPLETE 10) NO ATTIC VENT/COMBUSTION AIR 11) ATTIC ACCESS BLOCKED 12) TRAPPED WIRE AT POWER ROOM 13) POWER DUCT TRAPPED 14) FIRBLOCK GARAGE CHASE |
|
| 01/04/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) H20 HTR FLUE MINIMUM PITCH 60 DEGREE IRC G2427.6.4 2) MISSING S-1 PAGE IN PLAN SET CAN'T CHECK INTERIOR OR EXT. WALL H.D.'S IF ANY SEE GARAGE WALL 3) SECURE CUT STUD AT RANGE OUTLET KITCHEN 4) HAVE TRUSS MANUFACTURER CHECK NOTCH IN TOP CHORD KITCHEN CEILING FLAT FLOOR TRUSS 5) ATTIC FURNACE MINIMUM 1 SQUARE INCH FOR EVERY 1,000 BTU EACH FOR COMBUSTION AND RELIEF DUCTS 6) EAST BEDROOM NEEDS BANG PLATE INSIDE CORNER ROMEX 7) MISSING BEDROOM WINDOW EAST 2ND FLOOR 8) BLOCK AT TUB SURROUND SIDE 2ND FLOOR DRYWALL BACKING 9) LIVING ROOM SECURE CONDENSATE TO WALL |