Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM04388
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 04/10/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER SOFFITS. |
|
| 04/07/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH RACEWAYS AND WIRE PULL. 2. BOXES ARE OVERFILLED. 3. PAY REINSPECTION FEE. |
|
| 04/05/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED TO PAY REINSPECTION FEE 2. FINISH WIRING 3. FRAME ATTIC ACCESS OPENINGS |
|
| 04/04/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. COMPLETE WIRING CALL WHEN READY |
|
| 03/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK RACEWAY COVER 2ND LIFT -- PIPES ARE WRAPPED |
|
| 02/03/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST LIFT |
|
| 02/02/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* EMT CONDUIT, ELBOWS AND FITTINGS NEED PROTECTION FROM CORROSION (WALLS TO BE FILLED) PER NEC 358.10(B) OTHERWISE USE PVC OR ANOTHER METHOD APPROVED FOR CONCRETE FILL. |