Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM04384
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/20/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR SALES AREA DROP CEILING ONLY 1. EQUIPMENT GROUNDING CONDUCTOR #6 AND SMALLER TO BE PROPERLY IDENTIFIED -- NEC 250.119 2. PROPERLY SIZE EQUIPMENT GROUND ALL THE WAY THROUGH CKT FOR EQUIPMENT - NEC TABLE - 250.122 3. HAVE OVERFILLED BOXES - NEC 314.16 CHECK ALL J-BOXES, HAVE OPEN FOR INSPECTION PANELS NOT WIRES PER PLAN? |
|
12/15/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK BACK KITCHEN CEILING |