Permit: T05CM04384

Parcel: 12510004B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
12/27/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/20/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR SALES AREA DROP CEILING ONLY
1. EQUIPMENT GROUNDING CONDUCTOR #6 AND SMALLER TO BE PROPERLY IDENTIFIED -- NEC 250.119
2. PROPERLY SIZE EQUIPMENT GROUND ALL THE WAY THROUGH CKT FOR EQUIPMENT - NEC TABLE - 250.122
3. HAVE OVERFILLED BOXES - NEC 314.16
CHECK ALL J-BOXES, HAVE OPEN FOR INSPECTION
PANELS NOT WIRES PER PLAN?
12/15/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK BACK KITCHEN CEILING