Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/09/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROVIDE HOLDOWN FOR BACK-FED BREAKER NEC 408.16 (F) 2) INSTALL A GROUNDING ELECTRODE SYSTEM PER NEC 690.47 ? 3) CHECK NEC ARTICLE 690 FOR INSTALLATION COMPLIANCE 4) PROVIDE ROOF ACCESS |