Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2006 | FRAMING | Approved | ||
| 11/04/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PROVIDE CITY OF TUCSON STAMP ON SHEAR ENGINEERING LETTER |
|
| 11/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL RETRO FIT HOLDOWNS AT S.E. CORNER 2) PROVIDE ENGINEERS APPROVED DESIGN FOR RETRO HOLDOWN 3) STUCCO LATH MUST BE SECURED AT ALL ENDS, EDGES AND STUDS 4) IRC 602.3(3) NOTE 'B' REQUIRES OSB TO BE INSTALLED ACROSS STUDS 5) REPLACE OVER NOTCHED BEARING STUDS 6) PROVIDE DETAIL OF GARAGE SHEAR WALL 8 CONNECTION TO TRUSS SYSTEM 7) STOPPED INSPECTION-TO MANY ITEMS |
|
| 10/19/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) PROVIDE ENGINEER OF RECORD AND CITY OF TUCSON APPROVED REPAIR FOR SPAULED HOLDOWN 2) EXTERIOR CLIP NOT APPROVED CANNOT APPROVE STUCCO LATH 3) FRONT BEDROOM 3 SHEAR 2 X 12 SPLIT REPLACE 4) DBL GIRDER REQUIRES H2.5 ON EACH SIDE EACH ENT 4/SD3 5) NOTE 6 SHEARWALL SCHEDULE REQUIRES PANEL LONG DIMENSION ACCROSS STUDS WITH ENDS AND EDGES NAILED AT 4" ON CENTER 6) BEDROOM 3 SHEAR HOLD DOWN WRONG LOCATION. MUST BE AT END OF SHEARWALL 7) MTT 28 B HOLDOWNS MISSING NUTS 8) SHEARWALLS REQUIRE STUDS AT 16" ON CENTER (SHEAR SCHEDULE) 9) STOPPED INSPECTION TO MANY ITEMS |