Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL 1. LOW VOLTAGE SIDE OF GATE OPENER CONTAINS A WET CELL BATTERY. VERIFY IF FOR INSTALLATION IN CONTROL CABINET. |
|
| 04/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED LIGHT POLE CAP AND POLE BOND 2) CHECK GATE OPENER NEXT TIME 3) BOX BOND JUMPER TO BE 250.122 |
|
| 03/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CANNOT PASS THROUGH AC DISCONNECTS 2. MAINTAIN WORKING CLEARANCES 3. SECURE CABLE TO DISCONNECTS 4. LABEL DISCONNECTS 5. TURN SCREWS IN AT METAL BOXES FOR CLEARANCES - DEVICES 6. CIRCUIT LABELING TO BE AS PER 404.8 7. DISCONNECTING MEANS NEEDED FOR WATER HEATER 8. NEED RECEPTACLE FOR WALL SPACE -- 210.52 9. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NON-COMBUSTIBLES 314.20 10. SECURE CABLES TO BOXES -- 312.5 11. BOXES ARE NEEDED AT BATH LIGHTS 12. CLOSET LIGHTS TO BE AS PER 410.8 |