Permit: T05CM04340

Parcel: 12204043A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
1. LOW VOLTAGE SIDE OF GATE OPENER CONTAINS A WET CELL BATTERY. VERIFY IF FOR INSTALLATION IN CONTROL CABINET.
04/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED LIGHT POLE CAP AND POLE BOND
2) CHECK GATE OPENER NEXT TIME
3) BOX BOND JUMPER TO BE 250.122
03/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CANNOT PASS THROUGH AC DISCONNECTS
2. MAINTAIN WORKING CLEARANCES
3. SECURE CABLE TO DISCONNECTS
4. LABEL DISCONNECTS
5. TURN SCREWS IN AT METAL BOXES FOR CLEARANCES - DEVICES
6. CIRCUIT LABELING TO BE AS PER 404.8
7. DISCONNECTING MEANS NEEDED FOR WATER HEATER
8. NEED RECEPTACLE FOR WALL SPACE -- 210.52
9. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NON-COMBUSTIBLES 314.20
10. SECURE CABLES TO BOXES -- 312.5
11. BOXES ARE NEEDED AT BATH LIGHTS
12. CLOSET LIGHTS TO BE AS PER 410.8