Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL OK O/S WALLS OK TO COVER WEST WALL IN WALL FIXTURES WITH STUB OUT OF WALLS AT NORTH & SOUTH END WITH #12 UF -- NOTHING UNDERGROUND AT THIS TIME. |
|
| 09/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FAN BOXES OK MANDRILL PULLS 1 1/2" PLEASE PROVIDE MEGAOHMETER READINGS ON A COMPLANY LETTERHEAD FOR ALL 4-UNIT CONDUCTORS (ALL CONDUCTORS) |
|
| 09/13/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNIT #4 OK UNIT #3 EXCEPT FEEDER CONDUIT OK UNIT #2 EXCEPT FEEDER CONDUIT AND BOXES FOR FANS OK UNIT #1 EXCEPT FEEDER CONDUIT AND BOXES FOR FANS 1. BOXES FOR FANS TO BE RATED |
|
| 09/12/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROTECT CABLES AT STUDS 2. SUPPORT CABLES ABOVE PANEL 3. SECURE ALL CABLES TO PANEL WITH CONNECTORS. 4. FILL UNUSED OPENING IN BOXES 5. SUPPORT NM CABLE WITHIN 12" OF CANS CONNECTIONS 6. REPAIR CUT SHEATHING 7. SEPARATE CLASS 1 & CLASS 2 WIRING 8. CABLE CLAMPS FOR MULTIGANG BOXES BROKEN OUT 9. SHEATHING TO EXTEND 1/4" INTO BOXES 10. USE APPROVED FITTINGS TO SECURE CABLE TO EXHAUST FAN. |
|
| 09/11/2006 | ELECTRIC - INTERMEDIATE | Cancelled | CANCELLED PER CONTRACTOR PAGE #907-0054 | |
| 07/05/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* NO ONE ON SITE. NO NEW WORK UNNECESSARY CALLS MAY RESULT IN A REFEE PER ADMIN. CODES |
|
| 06/29/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO WORK READY |
|
| 06/26/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CONDUIT TO MASONRY 4 UNITS |