Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 03/05/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 03/01/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. PROVIDE LETTER FROM ARCH OR ENGINEER OF RECORD FOR USE OF ALUM. FEEDERS & CONDUIT SIZE CHANGE FROM PLANS. 2. DO NOT DAISY CHAIN GROUNDS TO BOND BUSHINGS UNLESS PROPER WIRE SIZE PER 250 NEC 3. RECEIVED LETTER OF TORQUE 4. OK U.G FOR SITE LTG. AT FRONT PARKING |
|
| 02/27/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. PROTECT CONDUIT FROM CORROSIION PER 300.7 2. PLEASE PROVIDE LETTER OF TORQUE PER INSPECTION DATED 6/20/06 3. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT OK PVC CONDUIT SIDEWALK TO GATE OPENER |
|
| 02/07/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK CONDUIT RUN PANEL TO WALL 2) OK TO WALL TO DUMPSTER 3) RECEIVED CHECK #13749 FOR $108.00 AFTER HOURS INSPECTION |
|
| 01/24/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. NO MORE THAN 360 DEG. IN RUN OK TO COVER UP TO 360 DEG. |
|
| 07/21/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE SERVICE TO WALL 2. MAIN BONDING JUMPER AT SERVICE TO BE SAME SIZE AS UFER 3. LABEL SERVICES W/ADDRESSES 4. DAYLIGHT CAN BE SEEN THRU ENTRY CONDUIT FROM OWNERS PANEL INTO SERVICE. 5. MANDREL SIZE LESS THAN 1 1/2" NOT RIGHT FOR 2" CONDUIT. |