Permit: T05CM04340

Parcel: 12204043A

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
04/10/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
03/05/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/01/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. PROVIDE LETTER FROM ARCH OR ENGINEER OF RECORD FOR USE OF ALUM. FEEDERS & CONDUIT SIZE CHANGE FROM PLANS.
2. DO NOT DAISY CHAIN GROUNDS TO BOND BUSHINGS UNLESS PROPER WIRE SIZE PER 250 NEC
3. RECEIVED LETTER OF TORQUE
4. OK U.G FOR SITE LTG. AT FRONT PARKING
02/27/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. PROTECT CONDUIT FROM CORROSIION PER 300.7
2. PLEASE PROVIDE LETTER OF TORQUE PER INSPECTION DATED 6/20/06
3. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT

OK PVC CONDUIT SIDEWALK
TO GATE OPENER
02/07/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK CONDUIT RUN PANEL TO WALL
2) OK TO WALL TO DUMPSTER
3) RECEIVED CHECK #13749 FOR $108.00 AFTER HOURS INSPECTION
01/24/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. NO MORE THAN 360 DEG. IN RUN
OK TO COVER UP TO 360 DEG.
07/21/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE SERVICE TO WALL
2. MAIN BONDING JUMPER AT SERVICE TO BE SAME SIZE AS UFER
3. LABEL SERVICES W/ADDRESSES
4. DAYLIGHT CAN BE SEEN THRU ENTRY CONDUIT FROM OWNERS PANEL INTO SERVICE.
5. MANDREL SIZE LESS THAN 1 1/2" NOT RIGHT FOR 2" CONDUIT.