Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2006 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
| 12/11/2006 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE PRODUCE APPROVED PLAN FOR WALL. YOU NEED TO PROVIDE PROPER COVERAGE FOR BOND BEAM STEEL. |
|
| 07/10/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* #1101 WEST WALL TO 20' |
|
| 07/05/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* #1101 WEST WALL TO 18'6" |
|
| 06/29/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* UNIT #1101 WEST WALL TO 14'8" |
|
| 06/27/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) UNIT #1101 E. WALL TO 17'-4"/20' |
|
| 06/26/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
| 06/21/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* #1102 WEST WALL TO 17'4" |
|
| 06/20/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* #1103 W. WALL TO 18' |
|
| 06/06/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* #1103 E. WALL TO 18'2", #1101 E WALL TO 17'4" |
|
| 05/31/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 12'7"-17'4" -- #1104 EAST & WEST WALLS. |
|
| 05/22/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* ALL WALLS TO 12'7 OK TO GROUT |
|
| 05/18/2006 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* NO ONE ON SITE. |
|
| 05/12/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* ALL WALLS TO 9'4" |
|
| 05/02/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* ALL WALLS TO 8'8" |
|
| 04/11/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* LINES B.1/D.1, B2/D2 |
|
| 04/10/2006 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* NO PLANS AT SITE |
|
| 04/06/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* LINES B5 - D5 A4-B4 0-4'8" |
|
| 01/24/2006 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO HAVE SPECIAL INSPECTION PER SPECIAL CONDITIONS ON PERMIT |
|
| 01/23/2006 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* 1) WHERE PLAN KEY NOTE "Q" DESIGNATED, THE VERTICAL REINFORCEMENT MUST BE (2) #5 REBARS. (4) #4 REBAR DOES NOT NECESSARLY EQUAL (2) #5 REBARS 2) THE LAP SPLICES FOR #5 REBAR IS 32". THIS MEASUREMENT IS FROM TOP OF STEM WALL TO TOP OF VERTICAL REBAR 3) HORIZONTAL REINFORCEMENT AT STEM WALL MUST BE CONTINOUS THROUGH CONTROL JOINTS, MAY NOT BE LAPPED WITHIN 8' ? A CONTROL JOINT AND NEED TO BE WRAPPED (DUCT TAPE IS ACCEPTABLE) REFERENCE DETAIL 14 ON SHEET S1.1 4) CALL FOR REINSPECTION UNDER THE ITEM 01010 (STEM WALL/RETAINING WALL) |