Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/11/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS 1. FINISH ITEMS #3 & 4 BEFORE FINAL. |
|
| 05/10/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT FLEX WITHIN 12" OF BOXES AND 4' AND PROTECT AT STUDS. 2. VDV CABLING TO BE AS PER 725.6 & 800.2 & 6 3. PLEASE VERIFY DERATING OF NEW CIRCUITS PER 310.15 4. FILL UNUSED OPENING IN PANEL. 5. SUPPORT M/C CABLE WITHIN 12" OF BOXES AND PROTECT AT STOPS. NOTE: BORDER NEON UNSAFE |