Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2007 | FRAMING | Approved | IVRS - Inspection :* 1) NEED TO ADD SMOKE DETECTORS 2) WILL RECHECK AT ALL FINALS 3) VENTING USED FOR GAS LINE MUST BE WATER/INSPECT PROOFED FOR FINALS |
|
| 05/30/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLIP ALL 2 X 6 RAFTERS H2.5 EACH SIDE 2) JUNCTION BOX S.E. CORNER AT RAFTER MUST BE ACCESSIBLE 3) BLOCK REGISTER BOOTS 3 SIDES 4) SECURE ALL ROMEX 8" FROM BOXES AND EVERY 4' THERE AFTER 5) NAIL PROTECT ABS THROUGHOUT BASE PLATES 6) NO WATER TEST DWV SYSTEM, POTABLE WATER OK 7) FURR-OUT GAS SLEEVE 8) MISSING GFCI OUTLET BATH WITH ? SINKS 9) HAD WIRE SMOKIES IN EXISTING BEDROOM 1 DUE TO ACCESSIBILITY 1 IN BEDROOM 1 IN HALLWAY ENTRANCE 10) SECURE PEX THROUGHOUT |
|
| 12/05/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRES MUST BE MADE UP IN BOXES 2) USE ROMEX CONNECTORS IN METAL BOXES AND GROUND METAL BOXES 3) INSTALL NAIL STOP STRAPS AS REQUIRED TO PROTECT ALL PIPES WHEN SHEETROCKING 4) PURPOSE OF 4" SIGNLE WALL THRU ROOF IN BATH ? 5) NO EXHAUST FAN IN BATH 6) NO GAS PIPE UNDER SLAB IN PLAN. IF USED, THE VENT MUST BE TO AN OBVIOUS LOCATION SO A LEAK WILL BE NOTICED. (NEAR THE GROUND, NOT ON THE ROOF) 7) ELECTRICAL HOME RUNS SHOULD BE ROUTED TO PANEL |