Inspection History Details
Permit: T05CM04310
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/10/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. FINISH FLOOR BOXES AND REMOVE TRASH FROM BOXES MAINTAIN 1/4" FROM BOX TO SURFACE. 2. INSTALL BATHROOM LIGHTING. 3. INSTALL DISHWASHER CORD. 4. OUTDOOR LIGHTS NOT AS PER PLANS. PLEASE REVISE PER OUTDOOR LIGHTING CODES. 5. EMERGENCY LIGHTING TO BE ON CIRCUIT FOR AREA SERVED 700.12 |
|
| 03/30/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CHECK SPEAKERS WHEN INSTALLED |
|
| 03/28/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL SPEAKERS AND SUPPORT AS PER CODES 310.00 & 725.6 |
|
| 03/22/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* NO WORK PROGRESS |
|
| 03/19/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT AS PER 300.11, 725.6 |
|
| 03/15/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) VDV CABELING TO BE SUPPORTED AS PER 300.11 |
|
| 03/08/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. VERIFY IF WATER HEATER IS FROM MANUFACTURER AS A CORD & PLUG CONNECTED APPLIANCE. 2. FINISH VDV CABLING TO INSPECT. |
|
| 01/26/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*OK SHELL LIGHTING OK DEMISSING WALL |