Permit: T05CM04310

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/10/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. FINISH FLOOR BOXES AND REMOVE TRASH FROM BOXES
MAINTAIN 1/4" FROM BOX TO SURFACE.
2. INSTALL BATHROOM LIGHTING.
3. INSTALL DISHWASHER CORD.
4. OUTDOOR LIGHTS NOT AS PER PLANS. PLEASE REVISE PER OUTDOOR LIGHTING CODES.
5. EMERGENCY LIGHTING TO BE ON CIRCUIT FOR AREA SERVED 700.12
03/30/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CHECK SPEAKERS WHEN INSTALLED
03/28/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) INSTALL SPEAKERS AND SUPPORT AS PER CODES 310.00 & 725.6
03/22/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
03/19/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT AS PER 300.11, 725.6
03/15/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) VDV CABELING TO BE SUPPORTED AS PER 300.11
03/08/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VERIFY IF WATER HEATER IS FROM MANUFACTURER AS A CORD & PLUG CONNECTED APPLIANCE.
2. FINISH VDV CABLING TO INSPECT.
01/26/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*OK SHELL LIGHTING
OK DEMISSING WALL