Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM04295
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2006 | FRAMING | Approved | IVRS - Inspection :* | |
03/30/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GARAGE SHEARWALL 7 NOT NAILED AT 3" ENDS AND EDGES 2) GARAGE SHEARWALL 7 REQUIRES ANCHOR BOLTS AT 16" ON CENTER 3) HOLDOWN NUTS LOOSE 4) A02A MISSING TRUSS BRACE 5) SHIM ALL HEADERS TO TRIMMERS AND CRIPPLES 6) SMOKE DETECTORS MUST BE 36" FROM AIR SUPPLY REGISTERS 7) ATTIC ACCESS TO A/C DISCONNECT OBSTRUCTED BY AIR HANDLER MUST HAVE 30" X 30" UNOBSTRUCTED ACCESS TO DISCONNECT |