Permit: T05CM04295

Parcel: 140325580


Addresses:

3970 E ISAIAH DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/31/2006 FRAMING Approved IVRS - Inspection :*
03/30/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE SHEARWALL 7 NOT NAILED AT 3" ENDS AND EDGES
2) GARAGE SHEARWALL 7 REQUIRES ANCHOR BOLTS AT 16" ON CENTER
3) HOLDOWN NUTS LOOSE
4) A02A MISSING TRUSS BRACE
5) SHIM ALL HEADERS TO TRIMMERS AND CRIPPLES
6) SMOKE DETECTORS MUST BE 36" FROM AIR SUPPLY REGISTERS
7) ATTIC ACCESS TO A/C DISCONNECT OBSTRUCTED BY AIR HANDLER MUST HAVE 30" X 30" UNOBSTRUCTED ACCESS TO DISCONNECT