Permit: T05CM04285

Parcel: 12412293A


Addresses:

301 S PARK AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM04285

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/27/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- EQUIP. GROUNDS SHOULD BE TERMINATED TO ENCLOSURE NOT NEUTRAL BAR IN SERVICE DISC. SW
- HAVE APPROVED FOR GROUNDING AT SERVICE TO BE USED AHEAD OF SERVICE MAIN DISCONNECT
- OK INSIDE PIPING
02/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER UNDERGROUND FROM DOCK J-BOX TO BOTH SLABS