Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/18/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO MOVE FURNITURE IN |
|
| 01/17/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE USE CORRECT COVERS FOR FLOOR BOXES 2) FINISH ITEMS 1 AND 9 OF PREVIOUS INSPECTION |
|
| 01/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*EXIT /EMERGENCY LIGHTING TO BE AS PER 700.12 MISSING BATHROOM WALL LIGHTS. WILL NEED AN EXTENDER RING AT LIGHTS LOBBY RECEPTION DESK NOT INSTALLED INSTALL FLOOR BOXES IDENTIFY ( COLOR CODE) A/C UNIT CONDUCTORS TIGHTEN LOOSE FITTINGS AT EXHAUST FANS REVISE EXISTING PANEL SCHEDULE VERIFY CONDUCTOR FILL FOR CONDUIT PLANS CALL FOR SERIES RATING LABEL AT SES |