Permit: T05CM04246

Parcel: 140378350


Addresses:

6786 S AQUILINE DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/09/2006 FRAMING Approved IVRS - Inspection :*
12/23/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO DWV WATER TEST
2) NAIL PROTECT PLUMBING
3) GIRDER REQUIRES POSTS AT KITCHEN CUT BY ?
4) FIREBLOCK KITCHEN NORTH COLUMN
5) SEWER VENT MUST BE 10 FEET FROM AIR INTAKE
6) MAKE UP AIR DUCT CONNECTION BROKEN
7) FURNACE B-VENT CANNOT ENTER CABINET, SEE PAGE 32 OF INSTALLATION MANUAL
8) NOTE: WIRES MUST BE MOVED TO REPLACE GIRDER POST
12/21/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER TIM