Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM04226
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2006 | FRAMING | Approved | IVRS - Inspection :* | |
07/31/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* A. APPROVED TO INSULATE WALLS ONLY B. 1. ANTI-SIPHON ON HOSE BIBS 2. SLEEVE CONDUCTORS THAT PASS THROUGH MASONRY WALLS. 3. FIREBLOCK @ CAT-5 WIRING IN GARAGE 4. APPROVED FIRESTOP REQUIRED BETWEEN FRAMING & MASONRY @ CEILING. 5. STAPLE WIRES 8" FROM BOX @ CORNER OF KITCHEN. 6. SEPARATE ALL WIRES FROM TRUSS GANG PLATES 7. FIRESTOP FLOOR/CEILING PENETRATIONS 8. CLEANOUT REQ'D 2ND FLOOR 9. FLUE @ FURNACE? 10. PROVIDE TRUSS SPECS 11. BLOCK DROP CEILINGS 12. CLIP STUDS UNDER STAIR STRINGER 4' OC 13. STOPPED INSPECTIONS |
|
07/20/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH ALL ITEMS FROM PREVIOUS INSPECTION 2) STOPPED INSPECTION |
|
07/18/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DRYER VENT BROKEN ABOVE 1ST FLOOR CEILING 2) A/C LINE SCRAPING ON FHA STRAP SOUTH WALL GARAGE 3) SEAL PENETRATION IN 2ND FLOOR 4) ROMEX NORTH WALL GARAGE CEILING PINCHED IN TRUSSES 5) REAR DOOR ROMEX ? AT SWITCH BOX 6) MOVE COMBUSTIBLES AWAY FROM CAN LIGHTS 7) BLOCKING IN KITCHEN SOUTH WALL PINCHING WIRES 8) 2ND FLOOR NORTH WALL CEILING WIRES PINCHED IN COILING 9) STOPPED INSPECTION |