Permit: T05CM04206

Parcel: 141092510


Addresses:

6585 E LADONNA LN


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM04206

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
01/03/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) PROVIDE CITY APPROVED TRUSS ENGINEERING DOCUMENTS FOR TRUSSES NOT BEARING ON BEARING POINTS
12/29/2005 EXT METAL CLIPS/EXT SHEATHING Cancelled CANCELLED PER TED OF US HOMES
12/28/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) TRUSS BEARING COMPLIED WITH
2) REPLACE A35'S AT BIRD BOARDS
12/21/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REFEE WILL APPLY
2) 1/SD3 NOT COMPLIED WITH
3) TRUSSES NOT PER PLAN OFFSET BEARING POINT
12/20/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1/SD3 (BLOCKING TO PLATE CONNECTION) NOT COMPLIED WITH-NAILS BENT OVER
2) NO ACCESS TO ITEMS 4 AND 5 FROM INSPECTION DATED 12/16/05
12/16/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1/SD3 (BLOCKING TO PLATE CONNECTION) NOT COMPLIED WITH
2) H2.5 MISSING ON GIRDER IN GARAGE
3) 8/SD3 ( CROSS BRACING 48" ON CENTER) NOT COMPLIED WITH AT BACK
4) BLOCKS TO BE NAILED THROUGH ROOF SHEATHING PER 8/SD3
5) TRUSS NOT NAILED WEST SIDE OF GARAGE