Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
04/07/2006 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) OK TO COVER WALL IN CARPORT 2) STRAPS HAVE BEEN INSPECTED 3) ALL ELSE NOT READY |
|
04/04/2006 | BUILDING - FINAL | Denied | 1) FILL OPEN KNOCKOUTS IN ELECTRIC PANEL 2) BEDROOM SMOKE DETECTORS MUST BE ON ARC FAULT CIRCUIT 3) MULTI LUGGED GROUNDS MUST BE SAME GAUGE WIRES 4) NEUTRAL WIRES MAY NOT BE MULTI LUGGED 5) NO POWER TO WATER HEATER 6) HOUSE NOT COMPLETE 7) STOPPED INSPECTION |