Permit: T05CM04198

Parcel: 10511040D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04198

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/30/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) MAKE SURE BOTH PANEL DIRECTORYS ARE MARKED CORRECTLY
11/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245$
1) LABEL PANEL DIRECTORY CORRECTLY
2) SEAL INTERIOR OF CONDUITS LEAVING WALK IN FREEZERS
3) USE BOX EXTENSIONS WHERE OUTLETS SIT BACK MORE THAN 1/4"
4) USE 6-32 SCREW FOR DEVICES (NOT SHEETROCK SCREWS)
5) EXTEND CONDUIT INTO DISCONNECT AT ICE CREAM MACHINE AND STRAP WHIP TO MACHINE
6) INSTALL TWO REMAINING CAN LIGHTS
11/22/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*OK TO COVER ELECTRICAL IN SUSP. CEILING