Permit: T05CM04198

Parcel: 10511040D

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T05CM04198

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*OK TO CLEAR SUBJECT TO BOND BEING POSTED FOR FUEL & TESTING POWER
11/16/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :VALLEY ENERGY
INSTALL BOND SCREW IN SERVICE DISCONNECT
INSTALL BOND BUSHING OR BOND LOCKNUT IN NIPPLE WHERE UNPROTECTED CONDUCTORS PASS THRU
INSTALL BOND BUSHINGS AT BOTH ENDS OF METAL CONDUIT USE AS RACEWAY FOR GROUNDING ELECTORDE CONDUCTOR
10/26/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) NIPPLE FROM GUTTER TO CT CAN NEEDS GROUNDING BUSHINGS BOTH SIDES AND ONE LOCK NUT MISSING
2) METER AND MAIN DISCONNECT OK-NEED LOAD SIDE PULLED