Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM04184
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL | |
09/27/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/26/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*1. A MANUFACTURER HOLD DOWN IS NEEDED FOR MAIN THAT IS BACK?? 408.16 | |
09/23/2005 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
09/23/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE COMPLETE #2 OF PREVIOUS INSPECTION 225.32 IS IN CONJUCTION WITH 225.31 | |
09/20/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) TIGHTEN LOOSE FITTINGS AT PANEL 2) WHERE IS PANEL MAIN AS PER 225.31 3) HAVE PLANS REVISED AND CITY APPROVAL STAMPED FOR DELETED ITEMS AND LOCATIONS 4) BOXES IN COMBUSTABLES TO BE FRESH 314.20 USE AN APPROVED EXTENDER RING - METAL NOT APPROVED |