Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/17/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. USE ITE - SIEMENS CK RATHER THAN CRHUSE HINDS. 2. FOR OWNER'S INFORMATION, SUB-PANEL AT REC ROOM THE PANEL DOES NOT HAVE A GROUNDING MEANS THEREFORE YOU CANNOT CONNECT A GROUND SYSTEM TO THIS PANEL THIS WILL HAVE TO BE TAKEN CARE OF FOR FINAL. 3. OUTSIDE LIGHTS PER THIS PLAN NOT INSTALLED YET NOR LIGHTING CONTACTOR ASSEMBLY, WILL NEED FOR FINAL OK TO USE EXISTING LIGHTING UNTIL THEN. 4. FINISH RESTROOM LIGHTING - TEMP C OF O SUBJECT TO ALL LIGHTING IN RESTROOMS FINISHED HAVE GLENN CALL ME 909-5184 |