Permit: T05CM04173

Parcel: 116277580


Addresses:

3276 W TUMAMOC DR

Inspection Status: Approved

Inspection History: STUCCO MESH

Date Description Inspector Results Comments
03/31/2006 STUCCO MESH Approved IVRS - Inspection :*
03/28/2006 STUCCO MESH Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED APPROVED TRUSS DRAWINGS
2) SECURE ELECTRIC WIRES AWAY FROM FLUE PIPES
3) NO H20 TEST DWV
4) INSTALL BANG PLATE NAIL PROTECTION ELECTRIC/PLUMBING THROUGHOUT
5) STRAP HEADERS AT BEARING
6) GAS TEST HOLDING 30 POUND TEST
7) I-JOISTS DON'T MATCH PLAN
8) CLIP INTERIOR BEARING WALLS ACCORDINGLY AND BOLTS
9) STOPPED INSPECTION
03/27/2006 STUCCO MESH Not ready for Inspection IVRS - Inspection :*