Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2005 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
| 11/03/2005 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :*DO NOT TAPE RATED WALLS UNTIL APPROVED!! 2 HR RATED WALLS REQUIRE THAT YOU STAGGER SEAMS AT SHEET ROCK. YOUR CUTOUTS ARE NOT ALLOWING THAT YOU NEED TO PROVIDE A LISTED FIRESTOP SYSTEM FOR ALL PENETRATIONS PLASTIC FRIDGE BOX MAY NOT BE IN RATED WALL-USE METAL BOX BE AWARE ABS PLASTIC LARGER THAN 2" DIAMETER USUALLY REQUIRES A COLLAR FOR FIRE STOP OK TO TAPE OTHER WALLS EXCLUDES FIRE WALL ON WEST SIDE |
|
| 11/02/2005 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* |