Permit: T05CM04161

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T05CM04161

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/06/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
03/01/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TO COVER SECONDARY CONDUITS
*NOTE* - INSTALL WARNING RIBBON MINIMUM 12" ABOVE CONDUITS - RECEIVED SERVICE REVISION LETTER TODAY.
01/30/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
01/24/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE CONDUCTORS RATED FOR DIRECT BURIAL
2) BURY CONDUCTORS PER NEC 300.5
3) CLOSE OFF UNUSED OPENINGS IN PANEL
4) DRIVE GROUND RODS FLUSH
5) PROVIDE LETTER REQUIRED FROM PREVIOUS INSPECTION
12/28/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) NEW SERVICE LOCATION AND NEW RACEWAY WIRING METHOD FOR SUB-PANEL FEEDERS NEED TO BE REVISED ON THE PLANS-OK TO COVER ELECTRICAL UNDER GROUND BASED ON REVISIONS BEING APPROVED
12/22/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*PLANS CALL FOR PANEL FEEDERS TO BE INSTALLED IN RIGID STEEL RACEWAYS.
PLANS CALL FOR SCH 40 PVC NOT TO BE USED ON JOB
IF ENGINEER IS OK WITH CHANGES, THEN I'M OK. THERE ARE NO CODE VIOLATIONS USING PVC FOR PANEL FEEDER RACEWAYS .
OK TO COVER WHEN NOTE IS SUPPLIED BY ENGINEER.