Inspection History Details
Permit: T05CM04161
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 03/01/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER SECONDARY CONDUITS *NOTE* - INSTALL WARNING RIBBON MINIMUM 12" ABOVE CONDUITS - RECEIVED SERVICE REVISION LETTER TODAY. |
|
| 01/30/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 01/24/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE CONDUCTORS RATED FOR DIRECT BURIAL 2) BURY CONDUCTORS PER NEC 300.5 3) CLOSE OFF UNUSED OPENINGS IN PANEL 4) DRIVE GROUND RODS FLUSH 5) PROVIDE LETTER REQUIRED FROM PREVIOUS INSPECTION |
|
| 12/28/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) NEW SERVICE LOCATION AND NEW RACEWAY WIRING METHOD FOR SUB-PANEL FEEDERS NEED TO BE REVISED ON THE PLANS-OK TO COVER ELECTRICAL UNDER GROUND BASED ON REVISIONS BEING APPROVED |
|
| 12/22/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*PLANS CALL FOR PANEL FEEDERS TO BE INSTALLED IN RIGID STEEL RACEWAYS. PLANS CALL FOR SCH 40 PVC NOT TO BE USED ON JOB IF ENGINEER IS OK WITH CHANGES, THEN I'M OK. THERE ARE NO CODE VIOLATIONS USING PVC FOR PANEL FEEDER RACEWAYS . OK TO COVER WHEN NOTE IS SUPPLIED BY ENGINEER. |