Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/17/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PAINT EXPOSED PVC WITH LATEX PAINT. BLOCK AND CLAMP EVERY 4' 2) 1/2" DUCT LINER NOT ADEQUATE R VALVE FOR EXPOSED DUCT ON ROOF. MUST BE MINIMUM 1" THICK AND HAVE R VALVE OF 8. R-6 FLEX DUCT INSIDE ROUND DUCT NOT ADEQUATE FOR EXPOSED DUCT ON ROOF 3) RECALL FOR INSPECTION 4) SCRATCH THE UNIT DATA PLATE NEXT TO THE BEAT STRIP INSTALLED, IF NONE THEN IDENTIFY AS SUCH |