Permit: T05CM04152

Parcel: 126131120


Addresses:

4656 E 14TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/18/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/17/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) MINIUM 10 PSI TEST TO BE ON ENTIRE SYSTEM WITH NO LOSS OF PRESSURE FOR 15 MINUTES
2) PROVIDE 3 GALV SCREWS AT EACH JOINT OF WATER HEATER FLUE VENT INCLUDING CAP ON ROOF
3) PROVIDE BONDING OF BLDG GAS PIPING #4 WIRE
4) PROVIDE AGA OR CSA APPROVED GAS VALVE AND FLE RATED FOR 65,000 BTU'S